Difference between revisions of "Heatweb BEMS Hat"
Line 39: | Line 39: | ||
|- | |- | ||
|2 x RS485 | |2 x RS485 | ||
|Independent lines for Modbus or bespoke protocols<br> | | | ||
Independent lines for Modbus or bespoke protocols<br> | |||
DIP switch selectable terminating resistors<br> | DIP switch selectable terminating resistors<br> | ||
One line DIP switchable for Modbus Slave Mode | One line DIP switchable for Modbus Slave Mode | ||
|- | |- | ||
|1 x M-Bus | |1 x M-Bus | ||
|For meter communications<br> | | | ||
For meter communications<br> | |||
On-board supply: 36V @ 30mA<br> | On-board supply: 36V @ 30mA<br> | ||
Device limit: 10 | Device limit: 10 | ||
|- | |- | ||
|Power Supply | |Power Supply | ||
|Nominal voltage: 12VDC<br> | | | ||
Nominal voltage: 12VDC<br> | |||
Current requirement: 3A<br> | Current requirement: 3A<br> | ||
Minimum supply voltage: 11.8V<br> | Minimum supply voltage: 11.8V<br> | ||
Line 55: | Line 58: | ||
|- | |- | ||
|Battery support | |Battery support | ||
|On-board rechargeable battery socket<br> | | | ||
On-board rechargeable battery socket<br> | |||
Maintains power to all systems (5V, 24V & 36V) during loss of supply<br> | Maintains power to all systems (5V, 24V & 36V) during loss of supply<br> | ||
Voltage monitoring with safe shutdown<br> | Voltage monitoring with safe shutdown<br> |
Revision as of 17:48, 4 October 2022
Feature | Specifcations |
---|---|
8 x thermistor inputs |
10k resistance temperature devices |
4 x universal inputs |
100Hz pulse signals |
4 x volt-free / pulse inputs |
100Hz pulse signals |
2 x change-over relays | 10A @ 36V |
4 x PWM inputs |
DIP selected pull-up resistors (5V) |
4 x PWM outputs | DIP selected pull-up resistors (5V/24V) |
4 x 0-10v outputs | 10mA peak current |
2 x RS485 |
Independent lines for Modbus or bespoke protocols |
1 x M-Bus |
For meter communications |
Power Supply |
Nominal voltage: 12VDC |
Battery support |
On-board rechargeable battery socket |
Real time clock | |
General purpose input button | |
3 x user definable LEDs | |
Fan control and connector |
The Heatweb BEMS Hat runs from a 12v dc supply, generating 5v for the board, 24v for valves, and 36v for M-Bus, using on-board dc-dc converters backed up by a rechargeable battery. A coin cell is used to power a real-time clock.
WiFi, Ethernet and Bluetooth are provided by the parent controller board.
A number of the inputs are universal, and can be switched between NTC, 0-10v, or volt-free / pulse inputs (jumper selected). This ability to alter the hardware setup increases versatility significantly.
The addition of M-Bus allows us to connect to heat meters as standard, making the board a stand alone solution to open-sourcing meter data, and to use meter data within control logic.
The battery backup allows us to safely shut-down all valves and the controls when power is removed. This overcomes a common problem with HVAC systems, where valves typically remain open, destroying network performance.