Difference between revisions of "Heatweb BEMS Hat"

From Open Source Controls Wiki
Jump to navigation Jump to search
(Created page with " Category:Hardware")
 
Line 3: Line 3:


[[Category:Hardware]]
[[Category:Hardware]]
* 8 x dedicated NTC temperature sensor inputs
* 3 x Universal inputs for volt-free contacts, 100Hz pulse signals, 0-10V or either 1k or 10k NTC thermistors
* 4 x volt-free / 100Hz pulse inputs
* 2 x 10A change-over relay outputs
* 4 x PWM inputs with jumper switched pull-up resistors
* 4 x PWM outputs with jumper switched pull-up resistors in both 5v and 24v
* 4 x 0-10v outputs
* 2 x RS485 lines for Modbus or bespoke protocols, with jumper switched terminating resistors
* On board Modbus for daisy chaining multiple boards to a single controller
* M-Bus meter communications
* On-board battery supported uninterruptable power supply
* Real time clock
* General purpose input button
* 3 x user definable LEDs
* Fan control and connector
* 12v power supply
* 24v uninterruptable output power for valves
* 5v uninterruptable output power for sensors
The Heatweb BEMS Hat runs from a 12v dc supply, generating 5v for the board, 24v for valves, and 36v for M-Bus, using on-board dc-dc converters backed up by a rechargeable battery.  A coin cell is used to power a real-time clock.
WiFi, Ethernet and Bluetooth are provided by the parent controller board.
A number of the inputs are universal, and can be switched between NTC, 0-10v, or volt-free / pulse inputs (jumper selected).  This ability to alter the hardware setup increases versatility significantly.
The addition of M-Bus allows us to connect to heat meters as standard, making the board a stand alone solution to open-sourcing meter data, and to use meter data within control logic.  
The battery backup allows us to safely shut-down all valves and the controls when power is removed.  This overcomes a common problem with HVAC systems, where valves typically remain open, destroying network performance.

Revision as of 23:00, 12 July 2022


  • 8 x dedicated NTC temperature sensor inputs
  • 3 x Universal inputs for volt-free contacts, 100Hz pulse signals, 0-10V or either 1k or 10k NTC thermistors
  • 4 x volt-free / 100Hz pulse inputs
  • 2 x 10A change-over relay outputs
  • 4 x PWM inputs with jumper switched pull-up resistors
  • 4 x PWM outputs with jumper switched pull-up resistors in both 5v and 24v
  • 4 x 0-10v outputs
  • 2 x RS485 lines for Modbus or bespoke protocols, with jumper switched terminating resistors
  • On board Modbus for daisy chaining multiple boards to a single controller
  • M-Bus meter communications
  • On-board battery supported uninterruptable power supply
  • Real time clock
  • General purpose input button
  • 3 x user definable LEDs
  • Fan control and connector
  • 12v power supply
  • 24v uninterruptable output power for valves
  • 5v uninterruptable output power for sensors


The Heatweb BEMS Hat runs from a 12v dc supply, generating 5v for the board, 24v for valves, and 36v for M-Bus, using on-board dc-dc converters backed up by a rechargeable battery.  A coin cell is used to power a real-time clock.

WiFi, Ethernet and Bluetooth are provided by the parent controller board.

A number of the inputs are universal, and can be switched between NTC, 0-10v, or volt-free / pulse inputs (jumper selected).  This ability to alter the hardware setup increases versatility significantly.

The addition of M-Bus allows us to connect to heat meters as standard, making the board a stand alone solution to open-sourcing meter data, and to use meter data within control logic.  

The battery backup allows us to safely shut-down all valves and the controls when power is removed.  This overcomes a common problem with HVAC systems, where valves typically remain open, destroying network performance.