barbican_discussion.json Monitoring Architecture all_lorawan.json All LoRaWAN Architecture meter_installation.json Principles of calculating flow rates from temperatures barbican_meter_locations.json Heat Meter and Sensor Locations heatweb_barbican_graph1.json Graph 1 heatweb_barbican_micronics_1.json Micronics Installation 1
Drawings
CHW_Art_Gallery_-_Temporary_Heat_Meter_Locations
Heat Meters
See Micronics Heat Meters for information on how to connect Micronics Heat Meters.
- Error creating thumbnail: Unable to save thumbnail to destination
The first Micronics heat meter provided data immediately as expected, matching values on the screen. This can be viewed in the Node-RED software in the debug window, where one can inspect the data telegrams being sent and received. [1, 3 ...] represents device 1, function code 3 (read register). The response should also start with [1, 3 ...]
- Error creating thumbnail: Unable to save thumbnail to destination
However, the second meter provided incorrectly formed responses and will require further investigation.